The Voltage Drop Formulas
Depending on the phase of the system, different multipliers are applied:
- Single Phase systems:
V_drop = (2 * K * I * L) / CM - Three Phase systems:
V_drop = (1.732 * K * I * L) / CM
Where:
- K (Resistivity): 12.9 for Copper, 21.2 for Aluminum.
- I (Current): Load current in Amperes.
- L (Distance): One-way length of the cable in feet.
- CM (Circular Mils): The cross-sectional area of the conductor. E.g. 10 AWG is 10,380 CM.
Conductor Materials comparison:
- • Copper: More conductive, smaller required gauge sizes, but more expensive.
- • Aluminum: Less conductive (approx 61% of copper), requires larger gauge sizes, but cheaper and lighter.
- • Fittings: Ensure aluminum connections use antioxidant compound to prevent corrosion.